Our Fire Protection Products
We PHENIX FIRE PROTECTION SYSTEMS Provide the following systems on Turnkey basis (Consultancy, Design, Detailed Engineering, supply Installation, Testing & Commissioning) as per NFPA, latest Fire Service Code and NFPA standards.
Hydrant System Accessories
Our range of Fire Hydrants Systems are standard fire detection system that can easily sense fire in the initial stage and can control it by automatically dialing the fire brigade station or other related authority and inform. To control the fire an optional automatic Carbon Di-Oxide discharger can also help. Fire Hydrant System is one of the most effective fire alarming systems.
The whole pipeline is kept under uninterrupted pressure with water. Whenever the hydrant valve is open, the pressure in the pipeline reduces drastically and jockey pump set which normally keeps the total system pressurized is unable to cope with the system demand which results in further fall in pressure. The further fall in pressure is perceived by the designated pressure switch and the main fire pump set starts automatically. Relying upon the type and sensitivity of the risk, diesel-engine powered fire pump set should also be installed having standby capacity of 100%. Some of the system components of fire.
It is a semi-automatic fire extinguishing system. A network of pipes is laid out counting upon the risk with hydrant valves placed at strategic places. The spacing or the distance between yard hydrants is guided by norms viz.
The entire range of ISI marked Hydrant Accessories - Landing Valves, Couplings, Branch Pipes, Special Nozzles, Fire Hoses, Monitors, Hose Boxes, Hose Reel Drums etc.
Single Headed Oblique Type Gun Metal Fire Hydrant Valve 2.5" (63mm), 75mm N.B. Flanged inlet, with 63mm Female inst. Outlet with Blank Cap and Chain as per IS:5290 with ISI mark (Flange O.D 200mm, PCD 160mm, 4 nos X 19mm dia holes) (Also available in Stainless Steel)
- 63mm GM Single Headed Hydrant Valve – Commercial (Flange O.D 185mm, ID 63mm, PCD 145mm)
- Also available in 38mm, 50mm – Standard Quality (GM)
Double Headed Gun Metal Hydrant Valve 2.5" (63mm) with two individually controlled 63mm Female Inst. outlets, with 100 mm N.B. Flanged Inlet, complete with male Blank Caps and Chains as per IS:5290 (Flange OD 220 mm, PCD 180mm, 8 nos X 19mm dia holes)
- Double Headed Hydrant Valve – Commercial (Flange OD 220mm, ID 100mm, PCD 180mm)
C.P. (Controlled Percolating) HOSE - Cotton/Synthetic Fibre, Circularly Woven Jacketted Controlled Percolating Fire Hose, treated against rot with mystox, 36 kg/cm2 burst pressure, 22kg/cm2 proof pressure as per IS:8423 with ISI mark.
- Sizes 50mm (2"), 63mm (2.5")
RRL (Reinforced Rubberlined) Fire Hose Type A - Cotton Synthetic Fibre, circularly Woven Jacketed Rubberized Fabric RRL Fire Hose, treated against rot with mystox 36 Kg/cm2 burst pressure, 22kg/cm2 proof pressure as per IS:636:88 type A with ISI Mark.
- Sizes 38mm (1.5") , 50mm (2"), 63mm (2.5"), 70mm (2. ¾ ")
RRL Fire Hose Type A - Non-percolating Fire Hose with outer jacket made from 100% high tenacity synthetic yarn, lined with seamless EPDM having 38kg/cm2 Burst pressure, 22 Kg/Cm2 Proof Pressure and 18KG/cm2 working pressure as per IS:636/1988 Type ‘A' ISI mark. (MAGMEX Brand)
- Sizes 38mm (1.5"),50mm(2"),63mm(2.5"),70mm(2. ¾ “)
RRL (Reinforced Rubberlined) EXTOCOAT - Fire Hose with outer special Elastomeric coating, circular woven Jacketed, 100% High tenacity Synthetic Yarn inert against mildew and rot lined with a special compound of synthetic rubber with 40 Kg/cm2 burst pressure, 22kg/cm2 proof pressure as per IS:636:88 Type A with ISI Mark.
- Sizes 38mm (1.5"),50mm(2"),63mm(2.5"),70mm (2. ¾ ")
RRL (Reinforced Rubberlined) Fire Hose Type B Non Percolating Fire Hose Completely composite construction circularly woven 3 layered synthetic jacketed fully encapsulated with a specially formulated elastomer, resistant against grease, oils, acids, ozone, fungus, alkalies, heat and other chemicals with outer design to facilitate a good grip, completely flexible and lightweight, no maintenance with 42Kg/cm2 burst pressure, 25kg/cm2 proof pressure, 18kg/cm2 working pressure as per IS:636:88 type B with ISI mark.
- Sizes 38mm(1.5"),50mm(2"),63mm(2.5"), 70mm (2. ¾ ")
High Pressure Fire Fighting Hose seamlessly woven with high grade synthetic yarns with EPDM rubber lining to ensure high protection against ozone and rot with burst pressure of 50kg/cm2 & proof pressure of 36 kg/cm2 as per IS:14933-2001 Type ‘A' with ISI Mark (INFERMEX Brand)
- Sizes 38mm(1.5"),50mm(2"),63mm(2.5"), 70mm (2. ¾ ")
High Pressure Fire Fighting Hose with special inert compound for higher degree of protection against corrosive chemicals, heat and ozone suitable for high pressure applications with burst pressure 50 kg/cm2 as per IS:14933-2001 Type-B with ISI Mark. (C-JET Brand)
- Sizes 38mm(1.5"),50mm(2"),63mm(2.5"), 70mm (2. ¾ ")
Delivery Hose coupling male & female Gun Metal 2.5"(63mm), inst. type 63mm X 63mm size as per IS: 903 with ISI mark. (Also available in Stainless Steel or Aluminium or Copper)
- Also available in 38mm, 50mm – Standard Quality – GM, Aluminium
Suction Coupling Gunmetal 4" Male & Female Round Threaded as per IS:902. (Available in 3" also)
- Also available in standard quality
Rubber Suction Hose - blend of natural / synthetic rubber compound with wire embedded between the reinforcement with corrugated outer layer as per IS:3549 with ISI Mark. (Type 1: WP-7 kg/cm2, Type 2: WP-10kg/cm2)
- Size: 3" or 4" or 6"
Single Hose Box - Wall mounting type in 600mm X 400mm X 250mm) size to accommodate 1 lengths of 7.5 mtr. or 15 mtr. or 30 mtr. hoses and a branch pipe with glass covered single door with lock and key arrangements.
- Available in MS or FRP
Double Hose Box - Wall mounting type in 750mm X 600mm X 250mm size to accommodate 2 lengths of 7.5 mtr. or 15 mtr. hoses and a branch pipe with glass covered double door with lock and key arrangements
- Available in MS or FRP For 30mtr. – 2 Lengths (Size 1200mm x 625mm x 250mm)
Hose Reel Drum, swinging wall mounting type made of mild steel sheet to accommodate 30mtr or 36.5mr of 19mm dia Rubber Hose with nozzle along with suitable bracket for fixing on the wall.
- Nozzle – ABS or Gunmetal or Aluminium Available with 24mm Hose also.
Rubber Hose for Hose Reel Drum – Made of natural / synthetic rubber with plain or corrugated finish as per IS:444 with ISI Mark (Type 1: WP-6 Kgf/cm, Type 2: WP-10 Kgf/cm)
- Size: 19mm or 24mm O.D.(Also available in Commercial Quality Double Braided)
Fire Hydrant Wet Riser System
Were risers are a form of internal hydrant for the fireman to use and are always pressurized with water. Wet risers are only required for buildings where the topmost floor is higher than 30.5 meters above the fire appliance access level.
Wet riser system comprises duty fire pump with standby pump discharging into a 150mm diameter riser pipe with landing valves at each floor and to which canvas hose with nozzles cab be connected to direct the water jet at the fire. A jockey pump is usually provided to maintain system pressure. For high rise buildings, each stage of the wet riser should not exceed 70.15 meters.
Automatic Sprinkler System
Although automatic sprinkler installations have been commercially available since 1882 and have since been installed in a steadily increasing range of industrial and commercial premises, is true to say that many facets of sprinkler protection are little understood. It may be worthwhile, therefore, to descri 0.+*-be briefly the basis principles involved. Sprinklers fixed on pipe work charged with water spaced at regular intervals installed throughout the protected building and are connected to a reliable water supply. When a fire occurs, only the sprinklers in the immediate vicinity of the fire automatically operate the discharged water to control the fire. Sprinklers are not so sensitive that they operate at a stage when prompt manual first aid operations still have a chance of success.
These factors limit the damage to very low proportions. The operation of any one sprinkler causes an alarm to sound to bring help to the scene so that the water may be shut off as soon as the fire has been extinguished. The value of the automatic sprinkler system in the eyes of Fire Insurance Companies whose estimate is based on actual calculations, is shown by the high annual rebates on fire insurance premium which are allowed to the owners of sprinklered premises. The rebates vary according to the risk and it is not possible to lay down any hard and fast rules. For approved installations conforming with the standards laid down by the Tariff Advisory Committee of India, the saving is seldom less than about 40% of the premium normally charged for the insurance of a corresponding risk without sprinklers.

SPRINKLER – Standard Response, Standard Coverage ½" BSPT, Chrome Finish K-Factor 5.6.
- Temperature Rating – 57, 68, 79 Deg. C.
- Mounting – Pendent, Upright, Sidewall & Concealed
- Available in Chrome Finish
- For concealed sprinkler cover plate is with white finish or chrome finish.
Medium Velocity Water Spray System
Medium Velocity Water Spray Nozzles has an external deflector, which discharges water in a directional cone shaped pattern of small droplet size. The water is uniformly distributed over the surface to be protected. The nozzle is used in deluge water spray system for special hazard fire protection application. As the design and intent of specific water spray system may vary considerably, a MV nozzle is made available in several combination of orifice sizes and spray angles.
The minimum desirable pressure to achieve a reasonable spray pattern is 1.4 Kg./Sq.cm. The water distribution pattern as shown in the graph in following pages is at an average pressure of 2.0 Kg/Sq.cm. The change in pressure between 1.4 to 3.5 Kg./sq.cm. does not affect considerable change in spray angle. The spray pattern shown is with indoor application. System designer must consider wind velocity while designing the system for outdoor application. Field obstruction if any affecting the spray pattern of the nozzle must also be considered. The nozzle may be oriented to any position which is deemed necessary to cover the hazard.
Some of the areas where this system is widely used are:
- Horizontal storage vessels (like LPG Bullets, NH3 storage tanks etc.)
- Vertical storage vessels (like benzene, xylene, toluene tank age etc.)
- Spherical storage vessels (like LPG bullets, spheres etc.)
- Spot protection (Protection of selective areas/ equipments)
Maintenance
Use Teflon tape or soft thread sealant on male thread of the nozzle. The nozzles must be hand tightened into the fitting. LIFECO make wrench must be used to tighten the nozzle unit into the fitting. Excessive tightening torque may result into serious damage to nozzle arms and the deflector which may affect spray pattern of the nozzle and it's performance.
It is recommended that water spray system be inspected regularly be authorized technical personnel. The nozzle must be checked for corrosion, external and internal obstruction, blockage if any. The nozzle should be cleaned or replaced if required. The system must be operated with optimum water flow at least twice in a year or as per the provision of NFPA or local authority having jurisdiction.
The owner is solely responsible for maintaining the water spray system and the components therein so that it performs properly in actual operating condition
Fire Fighting Pumps
Short Branch Pipe Gun Metal 63mm with Detachable Hexagonal Nozzle as per IS:903 with ISI Mark (Also available in Stainless Steel or Aluminium or Copper)
- Short Branch Pipe Gun Metal 63mm with Detachable Hexagonal Nozzle as per IS:903 with ISI Mark (Also available in Stainless Steel or Aluminium or Copper)
Water/Foam Nozzle – produce secondary aspirated (sometimes non aspirated) foam which have expansion ratio of 1:3 to 1:4 with Female BSP Thread Inlet.
Monitor NB | Flow IPM | Range* Mtrs Water / Foam |
|
---|---|---|---|
63 | 1880 | 5 | 44 |
75 | 2820 | 62 | 51 |
100 | 3760 | 72 | 61 |
150 | 7520 | 87 | 73 |
FAST ACTION NOZZLE – Dual pressure fire fighting nozzle, lightweight, made of aluminium extrusion, hand controlled, anodized for resistant of corrosion and wear, having arrangement for detent flows, to shut off pressure assistance flush without shutting down, slide type valve for turbulence free flow moulded rubber, teeth for full fill, power for gasket gribber inlet screen, pistol type grip for holding, flow straightness for quality jet stream and knob provision for switching from standard 100 PSI to emergency low pressure operation, suitable for flow of 900 lmp at 7 kg/cm2 with inlet of 63mm size. Weight 3.2 kg approx.
AQUAJET MULTIPUPOSE NOZZLE – pistol-grip fire fighting, hand-held nozzle made out of light weight alu. Alloy duly hard-anodised with solid bore tip and additional advantage of fog pattern at the same time. Nozzle 2 ½ “ (M) inst. / 1 ½ “ (F) thread / 2 ½ “ (F) thread. Approx. weight 2.25 kg.
SUPERFIRE MULTI GALLONAGE NOZZLE / UNILITE –Fire fighting nozzle, made of extruded all. Alloy hard anodized for resistance to corrosion and wear. Select ‘O' metic mode provides variable flow rates at 7 kg/cm2, 360-475-600-750 and 900 lpm and flush without shutting down. Spinning teeth ring form water curtain for cooling and operator's protection from heat. Ball valve operated flow control lever for shutting off. Inlet with 63mm male inlet conforming to IS:903, Piston grip for greater control
NUELITE NOZZLE – Professional fire fighting nozzle made of die-cast, al. alloy, having arrangement for constant flow at straight jet/wide angle fog and complete shut-off, with a pistol-grip, ball type shut-off valve with adjustable seat & suitable for flow of 400 lpm at 7 kg/cm2 with inlet of 63mm size conforming to IS:903
MEDIUM VELOCITY SPRAY NOZZLE – Made of Brass or SS with ½" BSPT end connections.
- K-factor: Metric - 22,30,35,41,51,64,79, 91 & 102
- Spray angle - 65°,80°,90°,100°,110°,120° & 140°
HIGH VELOCITY SPRAY NOZZLE – Made of Brass with ¾" BSPT end connections.
- K - Factor & Spray angle: Metric - K18 x 80°, K22x75°, K26x100°, K 32x 90°
Fog Nozzle (G.M.) having arrangement of jet, high pressure fog and complete shut off with 63mm male inst. Inlet, duly chromplated as per IS: 952.
- Also available in 38mm
Triple Purpose Nozzle (G.M.) (Universal branch pipe) having arrangement of jet, fine spray and shutoff with 63mm male inst. Inlet, duly chromplated as per IS: 2871
- Also available in 38mm
London Pattern (Hand Controlled) Nozzle (G.M.) having arrangement of Jet, Spray, Adjustable water curtain and shutoff with 63mm male inst. Inlet, duly chromplated.
Revolving Nozzle (G.M.) with 63mm male inst. Inlet duly chromplated as per IS:906 (Flange Connection also available)
Multi Purpose Spray Nozzle (G.M) for Water / Foam Spray having arrangement of Jet, fine spray, fog, complete shutoff with adjustable flow output with 63mm male inst. Inlet duly chromplated. (ELKHART DESIGN)
Jumbo / Mayura Curtain Nozzle capable of giving 180 deg. Curtain spray to 20' to 25' feet height with 63mm G.M. male inst. Inlet.
Superjet Water Monitor – Stand Post Type made out of IS:1239 Seamless Steel tubes, Hot dip galvanized, flanged inlet, G.M. Ball bearings Swivel joints with brass locking arrangements, permitting 360 deg. Horizontal, 80-45 deg. Vertical traverse, with Aluminium Alloy Nozzle with male threaded inlet as per IS:8442 with ISI Mark. (Available in GM Nozzle or with 63mm G.M. Female inst. Outlet)
MODEL | OPERATINGPRESSURE RANGEKg/cm2 | INLET FLANGE NB | PERFORMANCE*(at 7 Kg/cm2 pressure) | |
---|---|---|---|---|
FLOW Ipm | RANGE Mtrs | |||
63MM | 6 - 12 | 75 OR 100 | 1750 | 55 |
75MM | 6 - 12 | 100 | 2580 | 62 |
100MM | 7 - 12 | 150 | 3750 | 67 |
Superjet Water/Foam Monitor – Stand Post Type made out of IS:1239 Seamless Steel tubes, Hot dip galvanized, flanged inlet, G.M. Ball bearings Swivel joints with brass locking arrangements, permitting 360 deg. Horizontal, 80-45 deg. Vertical traverse, with Aluminium Alloy Foam Nozzle with pickup tube as per IS:8442 with ISI Mark.
MODEL | OPERATINGPRESSURE RANGEKg/cm2 | INLET FLANGE NB | PERFORMANCE*(at 7 Kg/cm2 pressure) | |
---|---|---|---|---|
FLOW Ipm | RANGE Mtrs | |||
63MM | 7 | 75 | 1750 | 50 |
75MM | 7 | 100 | 2580 | 60 |
100MM | 7 | 150 | 3500 | 64 |
GROUND MONITOR – made of light weight (18kg) aluminium alloy with nozzle for waterjet and universal nozzle for waterjet, fog, foam. Universal joint for free vertical and horizontal rotations fitted with three non return valve inlets.
Collecting Breech (GM) having 1 no. 63mm Female Inst. Inlet and 2 nos. 63mm Male Inst. outlet. As per IS:905
Dividing Breech (G.M.) having 1 no. of 63mm Male Inst. Inlet & 2 nos. 63mm Female Inst. Outlet as per IS:905
Controlled Dividing Breech (G.M) with Control Valve having 1 no. 63mm Male Inst. Inlet & 2 nos. 63mm Female Inst. Outlet with control.
Foam System
Foam Making Branch Pipe FB5X – Made from Aluminium Alloy with 63mm G.M. Male Inst. Inlet with Pickup tube – 225 LPM
Foam Making Branch Pipe FB2 – Made from Aluminium Alloy with 63mm G.M. Male Inst. Inlet with Pickup tube.
- FB2 – 225 LPM, FB10 – 450 LPM, FB20 – 900 LPM
Portable Inline Inductors – Made from Aluminium Alloy with 63MM G.M. Male Inst. Inlet in one hand and Female Inst. Outlet in other hand with Pick-up tube.
Model | Nominal Flow lpm (at 7 bars*) | Recommended Operating Pressure bars | Lenght mm | Weight Kgs |
---|---|---|---|---|
ILI 225 | 225 | 5 - 10 | 440 | 5.5 |
ILI 450 | 450 | 5 – 10 | 440 | 5.5 |
Medium Expansion Foam Branches – To produce stable, superior quality medium expansion foam with 63mm G.M. male inst. Inlet. (Made of SS 304 or Aluminium Barrel)
Model | Range Mtrs (at 3.5 bars inlet pressure) | Nominal Expansion | Lenght mm | Weight Kgs |
---|---|---|---|---|
MX 225 | 06 | 1:40 | 530 | 5.0 |
MX 450 | 08 | 1:40 | 615 | 6.2 |
High Expansion Foam Generators – To Generate large amount of HX Foam with 63mm G.M. inlet. (Made of SS 304 or Aluminium body/shell)
Model | Output M3/min (at inlet pressure) | Nominal Expansion | Approx Height mm | Approx WeightKgs |
---|---|---|---|---|
HX | 47 (at 3.5 bars) | 1:270 | 610 | 17.0 |
Mini Super | 60 (at 5.5 bars) | 1:310 |
Mobile Foam Trolley Unit – Portable Foam Mobile Trolley fitted with inline inductor and foam making branch pipe (without Hose & AFFF Liquid). Body is made of FRP or MS or SS
- Capacity: 100ltrs or 200ltrs
Aqueous Film Forming Foam – Synthetic based foam compound mixed with addition of fluorodensides processing the property to create the film of water solutions that floats on top of non-polar flammable liquids as per IS:4989 PART-2 with ISI Mark (Available in: 3% or 6% Foam Compound in 20 ltrs HDPE Can)
Protein Foam – Based on Hydrolised Protein with added foam stabilizers and metal salts used to produce low expansion foam and reliable agent for protection of hazardous non-polar flammable liquids as per IS:4989 PART-1 with ISI Mark. (Available in: 20 ltrs HDPE Can)
Fluoroprotein Foam – Specially formulated by combining selected fluorotensides with protein base and it produces aqueous film forming characteristics as per IS:4989 PART-3 with ISI Mark (Available in: 20 ltrs HDPE Can)
Alcohol / Polar Solvent Resistant Foam – Synthetic polyvalent foam forming liquid, Psuedo-plastic consisting of surface active substances and polymer additives used for rapid action on surface fires with resistance to contamination of Hydrocarbons and to dehydration of Polar solvents (Available in: 20 ltrs HDPE Can)
High Expansion Foam Compound – A special composition of surfactants solubilizers and antifreeze agent designed to produce foam with low drainage time, superior fluidity and fire resistance. (Available in: 20 ltrs HDPE Can)
Hazmat Foam – For controlling hazardous vapours and spills. (Available in: 20 ltrs HDPE Can)
Automatic Fire Alarm & Smoke Detection System
Fire detection and alarm systems are designed to provide warning of the outbreak of fire and allow appropriate fire fighting action to be taken before the situation gets out of control. As all systems are designed primarily to protect life, property, this places a great responsibility on the designer because each building will present a different set of problems in relation to the risk of fire and fire spread.Each fire detection and alarm system therefore must be specially designed to meet the requirements for each building.
The fire alarm system can either be operated automatically or manually. Automatic operation is via the detectors whereas manual operation is by breaking the glass at the manual call point (break glass unit).
To override the automatic operation of this system in case of its failure during a fire, use the nearest unit of the manual break glass.
Smoke Detectors
Capacity (Kg) | 1 | 2 | 3 |
---|---|---|---|
Range (in Mts) | 3-4 | 3-4 | 4-5 |
Discharge time-sec. | 8-10 | 8-10 | 20-25 |
Ouer Diameter(in mm) | 86 | 110 | 151 |
Over All Diameter (in mm) | 330 | 365 | 510 |
Test Pressure(Kg/Cm2) | 25 | 30 | 30 |
Charge Pressure(Kg/Cm2) | 10-12 | 10-12 | 10-12 |
FM-200 is a leading alternative to Halon has been manufactured by Great Lakes Chemical Corporation, which has been utilised in Kidde Fire Protection Marine FM-200 fire protection systems.
Fast and effective, the Kidde FM-200 has a low space and weight characteristics, along with environmental acceptability.
NOVEC 1230 DOES NOT Remove or reduce Oxygen! NOVEC 1230 is a synthetic/chemical fire suppression gas and extinguishes a fire by removing the free radicals or heat elements from the fire triangle. (Oxygen, Heat and Fuel). The concentration of Novec 1230 is typically between 5.3% to 5.6% of the room volume.